Abstract:
Power loss and reliability are concern of any power networks. This thesis try to address
these problems by integrating distributed generation in a network. Optimization part is
executed in two steps. Loss sensitivity factor is used to find the best location for
distributed generation and in second step genetic algorithm optimization is used to find
optimum size of distributed generation. The optimization uses minimization of active
power loss and sum of voltage deviation. The reliability improvement is also studied for
the base case and after allocation and rating of DG. The method is evaluated on 84 nodes
15 kV outgoing feeder 02 of Addis West substation. The feeder has fifty-five
transformers with a connected load of 12 MW. For base case analysis, all bus voltages
found to be within standard, 0.95 p.u - 1.05 p.u, for all load scenarios except at connected
load. For connected load analysis, bus numbers 68 possess a magnitude of 0.9482 p.u.
Sum of per unit voltage deviation of each bus for same load profile found to be 3.1271
p.u. Also, the highest base case active and reactive loss is calculated for connected load
scenario. The values found to be 552.7 kW and 331.6 kVAr. The reliability assessment
index of the feeder is far behind the Ethiopian Electric Agency standard. The agency
stated System Average Interruption Frequency Index (SAIFI) of 20 Int/Yr and System
Average Interruption Duration Index (SAIDI) of 25 Hr/Yr. Base case SAIFI and SAIDI
of the feeder are 144.68 Int/Yr and 115.32 Hr/Yr, respectively. Following the
optimization procedure, two 0.6 MW PV DGs are installed at bus 68 and 21. The result
shows improvement of all the targeted physical parameters of the feeder. Bus voltages are
maintained with in standard limit for all load profile scenarios. 10.52% reduction is found
for the sum of per unit voltage deviation. The best reduction of 16.25% in both active and
reactive loss is calculated for 50% load scenario. The improvement found for SAIFI and
SAIDI with integration of DGs is 10.35% and 10.42%, respectively.
Keywords: Distributed Generation, Voltage Profile, Reliability, Active Power